CHECK AT ECU TERMINAL <A/C CONTROL UNIT>




Terminal No.
Check items
Inspection conditions
Normal conditions
1 - 4
-
-
-
5
Foot area air outlet/main battery cooling selection damper motor (drive battery cooling side)
When the main battery moves to the cooling side
System voltage
When foot area air outlet is selected
0 V
6
Foot area air outlet/main battery cooling selection damper motor (foot area air outlet side)
When the main battery moves to the cooling side
0 V
When foot area air outlet is selected
System voltage
7
Heater water pump relay
Heater water pump relay: ON
1 V or less
8
-
-
-
9
Communication with the A/C-ECU
-
-
10
Earth of the A/C-ECU
-
-
11
Communication with the A/C compressor
-
-
12
-
-
-
13
Back-up power supply
-
System voltage
14
Earth
Always
0 V
15
Power supply
A/C relay: ON
System voltage
16
A/C pressure sensor
Refer to .
Refer to .
17
Heater inlet water temperature sensor
Temperature at the sensor 25°C (10 kΩ)
1.0 to 1.5 V
18
Heater outlet water temperature sensor
Temperature at the sensor 25°C (10 kΩ)
1.0 to 1.5 V
19
Sensor earth
Always
0 V
20
Sensor power supply
Electric motor switch: ON
5 V
21 to 23
-
-
-
24
Air recirculation/fresg air selection damper motor and potentiometer
Air recirculation/fresh air selection damper motor fresh air position
0 to 1.5 V
25
heater 12 V power supply
Electric motor switch: ON
System voltage
26 to 28
-
-
-
29
Heater water pump assembly input
Heater water pump assembly: ON
12 V
30
Air recirculation/fresh air selection damper motor
When moving to air recirculation position
System voltage
When moving to fresh air position
1 V or less
31
Air recirculation/fresh air selection damper motor
When moving to fresh air position
System voltage
When moving to air recirculation position
1 V or less
32
-
-
-
33
Heater output
At max. heater output
3.0 to 7.0V
34
Heater output
At max. heater output
3.0 to 7.0V
35
Heater output
At max. heater output
3.0 to 7.0V
36
Heater output
At max. heater output
3.0 to 7.0V